THIS MANUAL IS SUPPLEMENTAL TO
THE SEA FROST R-134a ENGINE DRIVE MANUAL.
INSTALLATION INSTRUCTIONS
CONDENSING UNIT LOCATION AND MOUNTING
The design of the Shore Assist allows placement of the air-cooled unit in an enclosed
space such as a cabin locker, sail locker or engine room. Intake air should be drawn in
from the cabin area to insure the coolest, driest air supply. Standard 4" duct hose may
be used. Discharge does not need ducting if a vent in the area allows warm air to
escape. Intake ducting from the exterior of the boat will cause damp salt air to be drawn
in reducing unit life. This will also increase below deck moisture. The SA-I is extremely
quiet.
An unducted SA-I in a poorly ventilated small space will heat the air,
lowering the capacity of the unit and possibly causing damage by
overheating the compressor.
Service access and installation requires that the front and left end (inlet/outlet side) be
exposed. The duct hose will require 4 inches of clearance past the end of the SA-I.
Mount the Shore Assist level. The compressor is at the bottom. The unit may be
bulkhead or platform mounted. Pilot holes have been predrilled for the # 8 x 3/8" self-
taping screws and aluminum angle clips, included with the system.
INSTALLATION REQUIREMENTS
Neither inlet nor outlet should ever be blocked.
Provide for driest, coolest air for intake (top air port on housing.)
Page view 0
1 2 3 4 5 6 7 8 9

Summary of Contents

Page 1

1 372 ROUTE 4 BARRINGTON, NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:[email protected] www.seafrost

Page 2

2 Total combined air duct length for intake and discharge should not exceed six feet.  Only the intake needs ducting if the area is vented t

Page 3

3 WARNING: The SA-I unit is shipped under some nitrogen pressure. Before removing the caps on the Swagelok fittings, remove t

Page 4

4 HANDLING", "PROCEDURES FOR WORKING WITH R-134a". Attach clean, purged gauges to the suction service port on the compressor. This

Page 5

5 adjustment. Be sure valve is dry before final cap replacement. Operate for 30 minutes to confirm proper valve setting and operation. The

Page 6

6 the high side pressure will be 80 to 135 psi depending on the air temperature (50 to 95 degrees F.) through the unit. Almost immediately upon star

Page 8

8 THERMOSTAT CALIBRATION INSTRUCTIONS Note: Be sure that the unit is operating properly before making any thermostat adjustments. The sensing

Page 9

9 HOLDOVER PLATES STAINLESS STEEL EVAPORATOR PLATES