2 Total combined air duct length for intake and discharge should not exceed six feet. Only the intake needs ducting if the area is vented t
3 WARNING: The SA-I unit is shipped under some nitrogen pressure. Before removing the caps on the Swagelok fittings, remove t
4 HANDLING", "PROCEDURES FOR WORKING WITH R-134a". Attach clean, purged gauges to the suction service port on the compressor. This
5 adjustment. Be sure valve is dry before final cap replacement. Operate for 30 minutes to confirm proper valve setting and operation. The
6 the high side pressure will be 80 to 135 psi depending on the air temperature (50 to 95 degrees F.) through the unit. Almost immediately upon star
7
8 THERMOSTAT CALIBRATION INSTRUCTIONS Note: Be sure that the unit is operating properly before making any thermostat adjustments. The sensing
9 HOLDOVER PLATES STAINLESS STEEL EVAPORATOR PLATES